Tech Support 1.888.4DMP TECH

Average wait for the last ½ hour is 2m 30s

TECH SUPPORT FAQ

     

Modem Ile Limitations

August 25, 2000

It has come to our attention that a limitation of the Radionics Modem Ile format and the D6500 Receiver significantly affects the DMP XR200 and the XR200-485 when using M2E communication. The D6500 using the Modem IIe format can only receive zone numbers up to 255 and user numbers up to 254. Zone numbers 256 to 299 and user numbers 255 to 999 cannot be received by the D6500.